DB2000 Series Digital Indicating Controller
The DB2000 series is a 96 X 96mm digital indicating controller with the indicating accuracy of ±0.1% and the control cycle of approximately 0.1 seconds. The configuration of highly functional system is enabled by various options including 2 transmission signal outputs, 2 communications ports and arbitrarily-allocation of digital inputs.
Features
- Large easy-to-view 5-digit display
- Highly-functional operation screen and settings screen
- Outstanding controllability
- Versatile control functions provided
- Communications 2-port type provided
- Transmission signal 2-output type available
- READY function provided
- DI arbitrarily-allocation
- Heater disconnection alarm
- Conforming to international safety standards and European directives (CE)
- Conforming to RoHS
Models
Control mode(Output No.1) | Types |
---|---|
ON-OFF pulse type PID | DB20100000 |
ON-OFF servo type PID(Standard load specification) | DB20200000 |
Current output type PID | DB20300000 |
SSR drive pulse type PID | DB20500000 |
Voltage output type PID | DB20600000 |
ON-OFF servo type(Very light load specification) | DB20800000 |
*Input signal:Universal input
Input Specifications
Input type | Thermocouple B, R, S, K, E, J, T, N, WRe5-WRe26, W-WRe26, NiMo-Ni, CR-AuFe, PR5-20, PtRh40-PtRh20, Platinel II, U, L DC voltage ±10mV, ±20mV, ±50mV, ±100mV, ±5V, ±10V DC current 0 to 20mA Resistance thermometer Pt100, JPt100, Old Pt100, JPt50, Pt-Co |
---|---|
Accuracy rating | ±0.1% of measuring range ± 1 digit *For details, refer to [Detailed specifications of accuracy ratings]. |
Reference junction compensation accuracy | K, E, J, T, N, Platinel II — ±0.5°C or
a value equivalent to ±20µV, whichever
is greater (at ambient temperature of 23°C ± 10°C) Others — ±1.0°C or a value equivalent to ±40µV, whichever is greater |
Sampling rate | Approx. 0.1 seconds |
Display Specifications
Display element | Upper display LED Lower display LCD (with back light) 108 x 24 dots |
---|---|
Display content | Upper display PV 5-digit, SV 5-digit, status indications, etc. Lower display MV, output status, setting screens, etc. |
Control Specifications
Control cycle | Approx. 0.1 seconds |
---|---|
Output type | ON-OFF pulse type, ON-OFF servo type, Current output type, SSR drive pulse type, Voltage output type |
Setting Specifications
SV relations | SV 8 types (maximum 5 digits setting) SV range SV rate-of-change |
---|---|
Control relations | PID 8 types P : 0 to 999.9% I : 1 to 9999 seconds D : 0 to 9999 seconds A.R.W. (Anti reset windup) High limit — 0 to 100.0% Low limit — -100 to 0.0% |
Alarm Specifications
Number of alarm points | 4 points |
---|---|
Alarm types | Absolute value alarm, deviation alarm, absolute value deviation alarm, setting value alarm, output value alarm, control loop abnormality alarm, FAIL, timer |
Output signal | Relay output signal (a contact) |
General Specifications
Rated power voltage | General power supply specifications 100 to
240VAC 24V power supply specifications 24VAC/24VDC |
---|---|
Rated power supply frequency | General power supply specifications 50/60Hz 24V power supply specification 50/60Hz (24VAC) |
Maximum power consumption | General power supply specifications Without options 100VAC 10VA/240VAC 15VA 24V power supply specifications Without options 24VAC 10VA/24VDC 5W |
Working temperature range | -10 to 50°C |
Working humidity range | 10 to 90%RH |
Color | Gray or black |
External dimensions | 96 (H) x 96 (W) x 127 (D) *The depth from the front panel is 120mm |
Weight | Without options Approx. 450g |
Safty Standard
CE | EN61326: 1997 +A1+A2+A3 EN61010-1: 2001 (Overvoltage category II, pollution degree 2) |
---|---|
UL | UL61010-1 2nd edition |
c-UL | CAN/CSA C22.2 No.61010-1-04 |