Graphic Program Controller/Setter DP-G Series

The DP-G Series is a successor to the DP Series high-functional program controllers and program setters, which have been enjoying high patronage for many years. It adopts a 5.6-inch color liquid crystal display with the accuracy of 0.1% and the sampling rate of 0.1 second, offering a high level of visibility in operations and settings and advanced monitoring screens. It can store up to 200 types of program patterns and up to 4000 steps.

  • Easy-to-view color liquid crystal display provides great visibility into various data such as program patterns
  • In addition to collective display, various monitoring screens are available including enlarged numeric display, bar graph display and trend display
  • Easy-to-use setting menu in Japanese
  • 28-point contact output, 16-point contact input, analog transmission output (option) and communication interface (option) are provided, allowing easy system construction
  • Comes as standard with parameter editing software for PC
  • The setter model provides a digital output type, allowing error-free program pattern signal output

 

List of Types

Controller

Adjustment mode (1st output) Case color
Gray Black
ON-OFF pulse type DP1010G000-G10 DP1010G000-B10
ON-OFF servo type (standard load specification) DP1020G000-G10 DP1020G000-B10
Current output type DP1030G000-G10 DP1030G000-B10
SSR drive pulse type DP1050G000-G10 DP1050G000-B10
Voltage output type (general type) DP1060G000-G10 DP1060G000-B10
ON-OFF servo type (minute load specification) DP1080G000-G10 DP1080G000-B10
Current output type (high accuracy type)
4 mA to 20 mA DC
DP10A0G000-G10 DP10A0G000-B10
Current output type (high accuracy type)
1 mA to 5 mA DC
DP10B0G000-G10 DP10B0G000-B10
Voltage output type (high accuracy type)
0 V to 10 V DC
DP10C0G000-G10 DP10C0G000-B10

Setter

Setting output signal Case color
Gray Black
Digital output (RS-422A) DP3-10G000-G10 DP3-10G000-B10
Analog output (4 mA to 20 mA) DP3-20G000-G10 DP3-20G000-B10
Analog output (0 V to 10 V) DP3-40G000-G10 DP3-40G000-B10
Analog output (0 V to 1 V) DP3-50G000-G10 DP3-50G000-B10
Digital output (RS-485) DP3-70G000-G10 DP3-70G000-B10

*DP2000G for wide area control is also available. Contact us for details.

Specifications

Controller specification

Input signal Thermocouple: B, R, S, K, E, J, T, etc.
DC voltage: ±10 mV, ±20 mV, ±50 mV, ±100 mV, ±5 V, ±10 V
DC current: 20 mA
Resistance thermometer: Pt100, JPt100, etc.
Accuracy rating ±0.1% of input span ±1 digit (under standard operating conditions)
* There are separate detailed rating descriptions.
Reference junction compensation accuracy K, E, J, T, N, Platinel II: ±0.5°C or lower
Other than above: ±1.0°C or lower
Sampling rate Approx. 0.1 second
Burnout Burnout is provided as standard for thermocouple, DC voltage (±50 mV or less) and resistance thermometer.
Rated power supply voltage 100 V to 240 V AC 50/60 Hz (universal power supply)
Weight Approx. 1.7 kg
Output format Current output type, ON-OFF pulse type, Voltage output type, SSR drive pulse type
Adjustment setting value PID 8 types
P: 0% to 999.9% (0 for 2 position operation)
I: 0 to 9999 seconds (0 is equivalent to infinity)
D: 0 to 9999 seconds
ON-OFF pulse type Output signal: ON-OFF pulse conductive signal
Contact capacity: Resistive load 100 V to 240 V AC 30 V DC, 5 A or less
Inductive load 100 V to 240 V AC 30 V DC, 2.5 A or less
ON-OFF servo type Output signal: ON-OFF servo conductive signal
Contact capacity: Standard load specification:
Resistive load 100 V to 240 V AC 30 V DC, 5 A or less
Inductive load 100 V to 240 V AC 30 V DC, 2.5 A or less
Minute load specification:
Resistive load 100 V to 240 V AC 30 V DC, 20 mA or less
Inductive load 100 V to 240 V AC 30 V DC, 20 mA or less
Current output type Output signal: 4 mA to 20 mA DC or 1 mA to 5 mA
Load resistance: 750 Ω or less
SSR drive pulse type Output signal: Output voltage:
ON-OFF pulse voltage signal ON voltage 12 V DC ±20%
OFF voltage 0.8 V DC or lower
Output signal Output signal: 0 V to 10 V
Output impedance: Approx. 10 Ω
Number of alarm points 4 points + 4 points (extended allocation setting)

Setter specification

Output signal Analog output 4 mA to 20 mA DC, 0 V to 1 V DC, 0 V to 10 V DC
Digital output RS-422A, RS-485
Output update cycle 0.1 second
Accuracy rating ±0.1% of output span
Resolution Approx. 1/50000
Output impedance Approx. 10 Ω
Load current Current output 400 Ω or less, Voltage output 50 kΩ or more