What information is included in the "analog input data" (measured value) that can be read via communication?

analog data read (Read)

Through communication, the following important analog data measured by the JW Series main unit can be read.

Measurement items Reference number (example) Details (average data)
Voltage value (average) 31101 The average rms value of load voltage.
current value (average) 31104 The average rms value of load current.
Power value (total) 31107 Measurement of the total power for all three phases.
load resistance 31110 load resistance value guideline (rated value conversion).
Phase-to-phase voltage 31113 (between UV) and others The voltage between each phase between UV, VW, and WU.
Each phase current 31116 (U phase) and others current for U, V, and W phases.
Initial resistance 31180 (U phase) and others The initial resistance value that serves as the heater disconnection alarm judgment standard.

Note: display voltage and current values are handled as 16-bit integer values over MODBUS communication.
To convert to actual physical quantities (V, A, kW, etc.), you must separately obtain information about the "decimal point position" (e.g., reference numbers 31102, 31105, etc.) and apply appropriate scaling.